横河AAM11输入模块AAM11输入卡
AMN11 模拟输入/输出模块箱
AMN12 快速模拟输入/输出模块箱
AMN21 继电器输入/输出模块箱
AMN31 输入/输出端子模块箱
AMN32 输入/输出接插件模块箱
AMN33 通信模块箱
AMN34 多点控制模拟输入/输出模块箱
AAM10 电流/电压输入模块
AAM11 电流/电压输入模块
AAM11B 电流/电压输入模块(支持 BRAIN)
AAM21 mV,热电偶和 RTS 输入模块
AAM21J mV,热电偶和 RTS 输入模块(符合 IEC584-1995,IEC751-1995)
APM11 脉冲输入模块
AAM50 电流输出模块
AAM51 电流/电压输出模块
AMM12T 电压输入多路变换器模块(16 点,端子型)
AMM12C 电压输入多路变换器模块(16 点,接插件型)
AMM22M mV 输入多路变换器模块(16 点,端子型)
AMM22T 热电偶输入多路变换器模块(16 点,接插件型)
AMM22TJ 热电偶输入多路变换器模块(16 点,端子型,符合 IEC584-1995)
AMM22C mV 输入多路变换器模块(16 点,接插件型)
AMM32T RTD 输入多路变换器模块(16 点,端子型)
AMM32TJ RTD 输入多路变换器模块(16 点,端子型,符合 IEC751-1995)
AMM32C RTD 输入多路变换器模块(16 点,接插件型)
AMM32CJ RTD 输入多路变换器模块(16 点,接插件型,符合 IEC751-1995)
AMM42T 2 线制变送器输入多路变换器模块(16 点,端子型)
AMM52T 电流输出多路变换器模块(16 点,端子型)
ADM11T 接点输入模块(16 点,端子型)
ADM11C 接点输入模块(16 点,接插件型)
ADM12T 接点输入模块(32 点,端子型)
ADM12C 接点输入模块(32 点,接插件型)
ADM51T-1
ADM51T-2 接点输出模块(16 点,端子型)
ADM51C-1
ADM51C-2 接点输出模块(16 点,接插件型)
ADM52T-1
ADM52T-2 接点输出模块(32 点,端子型)
ADM52C-1
ADM52C-2 接点输出模块(32 点,接插件型)
ADM15R 继电器输入模块(16 点,端子型)
ADM55R-1
ADM55R-2 继电器输出模块(16 点,端子型)
ACM11 RS-232C 通信模块
ACM12 RS-422/RS-485 通信模块
ACF11 现场总线通信模块
AMC80 多点控制模拟输入/输出模块
AAM11 电流/电压输入模块
AAM11B 电流/电压输入模块(支持 BRAIN)
Analog I /O Module
Current/Voltage Input Modules
These modules receive 4-20 mA from 2-wire transmitters and 1-5 V standardized signals. They can also receive signals other than standard 4-20 mA or 1-5 V signals. AAM11B can be combined with a transmitter which supports BRAIN communications. Use our BRAIN terminal to specify parameters for a transmitter.
Items |
Specifications |
|
Model |
AAM11, AAM11B |
|
Input signal |
0 to 10 V DC |
0 to 20 mA DC (*1) (*2) (It is possible to supply power to a transmitter.) |
Input resistance |
1 MΩ at power-up (100 kΩ at power-down) |
250 Ω |
Allowable input voltage/current |
-10 to 30 V DC |
40 mA DC or less |
Supplying power to transmitter |
- |
25.0 to 25.5 V DC (Output current limit: 60 mA DC or less ) |
Auxiliary voltage output |
1 to 5 V DC; Output resistance: 1 Ω or less; Allowable load resistance: 10 kΩ or more; Signal ground is shared with system |
|
Square root extraction |
Specify whether to use square root extraction. |
|
Accuracy |
Voltage input: ±4 mV; Current input: ±16 µA; Auxiliary voltage output: ±12 mV |
|
Effect of ambient temperature change |
For 10 °C change: Voltage input: ±4 mV + ± 0.15 % of specified value Current input: ±32 µA Auxiliary voltage output: ±24 mV |
|
Data update period |
50 ms |
|
Current consumption |
300 mA or less (5.0 V DC) |
|
Signal isolation |
Input signals are isolated between systems Withstanding voltage: 1500 V AC/min |
|
How installed |
Installed in the I/O Module Nest |
|
How connected |
Connected to the terminals of the I/O Module Nest with M4 screws |
|
How input signals are specified |
Specify input signals and range by software setting. |
*1: This module can be combined with MTL barrier 728. In this case, wiring resistance must be 10 Ω or less and the minimum operating voltage of the 2-wire transmitter must be 12 V DC or less.
*2: When the power of AAM11 is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current signals with other receivers. To share signal, attach Shunt Resistance (250 Ω) to current-output module and share voltage output.