AMN11 模拟输入/输出模块箱
AMN12 快速模拟输入/输出模块箱
AMN21 继电器输入/输出模块箱
AMN31 输入/输出端子模块箱
AMN32 输入/输出接插件模块箱
AMN33 通信模块箱
AMN34 多点控制模拟输入/输出模块箱
AAM10 电流/电压输入模块
AAM11 电流/电压输入模块
AAM11B 电流/电压输入模块(支持 BRAIN)
AAM21 mV,热电偶和 RTS 输入模块
AAM21J mV,热电偶和 RTS 输入模块(符合 IEC584-1995,IEC751-1995)
APM11 脉冲输入模块
AAM50 电流输出模块
AAM51 电流/电压输出模块
AMM12T 电压输入多路变换器模块(16 点,端子型)
AMM12C 电压输入多路变换器模块(16 点,接插件型)
AMM22M mV 输入多路变换器模块(16 点,端子型)
AMM22T 热电偶输入多路变换器模块(16 点,接插件型)
AMM22TJ 热电偶输入多路变换器模块(16 点,端子型,符合 IEC584-1995)
AMM22C mV 输入多路变换器模块(16 点,接插件型)
AMM32T RTD 输入多路变换器模块(16 点,端子型)
AMM32TJ RTD 输入多路变换器模块(16 点,端子型,符合 IEC751-1995)
AMM32C RTD 输入多路变换器模块(16 点,接插件型)
AMM32CJ RTD 输入多路变换器模块(16 点,接插件型,符合 IEC751-1995)
AMM42T 2 线制变送器输入多路变换器模块(16 点,端子型)
AMM52T 电流输出多路变换器模块(16 点,端子型)
ADM11T 接点输入模块(16 点,端子型)
ADM11C 接点输入模块(16 点,接插件型)
ADM12T 接点输入模块(32 点,端子型)
ADM12C 接点输入模块(32 点,接插件型)
ADM51T-1
ADM51T-2 接点输出模块(16 点,端子型)
ADM51C-1
ADM51C-2 接点输出模块(16 点,接插件型)
ADM52T-1
ADM52T-2 接点输出模块(32 点,端子型)
ADM52C-1
ADM52C-2 接点输出模块(32 点,接插件型)
ADM15R 继电器输入模块(16 点,端子型)
ADM55R-1
ADM55R-2 继电器输出模块(16 点,端子型)
ACM11 RS-232C 通信模块
ACM12 RS-422/RS-485 通信模块
ACF11 现场总线通信模块
AMC80 多点控制模拟输入/输出模块
AMC80 多点控制模拟输入/输出模块
This module controls 8-point analog loop. It can be made redundant.
Item |
Specifications |
|
Model |
AMC80 |
|
Input |
No. of input points |
8 |
Input signal |
1 to 5 V DC (differential, non-isolated inputs) |
|
Input resistance |
500 kΩ or more (at power-up)/100 kΩ or more (at power-down) |
|
Allowable input voltage |
-30 to 30 V DC |
|
Accuracy |
± 4 mV |
|
Effect of ambient temperature change |
For 10 °C change: ±8 mV |
|
Input data update period |
45 ms |
|
Step response time |
300 ms |
|
Input signal isolation |
No isolation between system and field, and between channels |
|
Allowable common mode voltage |
±5 V or less |
|
Output |
No. of output points |
8 |
Output signal |
4 to 20 mA DC |
|
Output resistance |
500 kΩ or more |
|
Allowable load resistance |
0 to 750 Ω |
|
Output range |
1.25 to 22 mA |
|
Output current |
25.5 V DC or less |
|
Output open detection |
0.65 mA or less |
|
Output accuracy |
± 48 µA |
|
Effect of ambient temperature change |
For 10 °C change: ±32 µA |
|
Output data update period |
45 ms |
|
Output step response |
100 ms |
|
Output signal isolation |
No isolation between system and field, and between channels |
|
Current consumption |
2 A or less (5 V DC) |
|
How installed |
Installed in the AMN34 Nest for |
|
Wiring |
KS1 cable |